ST student server was down when I got in today. Checked logs – couldn’t find any problems. Processor was at 24%. Couldn’t do anything useful at the console. Tried to check connections in the “monitor” screen – no response. Spawned other command lines – no response from “speed” or “down”. Powered off the server – it appeared to start up normally.

Webmail and wireless services slow

InfoSys is working to identify the source of heavy load on the server hosting Webmail and wireless authentication services. Until the problem is diagnosed and resolved Webmail service may be periodically disrupted and users may not be able to authenticate to the EMU wireless network. We are doing everything possible to resolve the situation rapidly and we apologize for the inconvenience.

UPS Failure During Diagnostics

During diagnostic procedures following UPS failure of 3/6, the affected UPS failed again. This caused a number of single-source power supply serversDuring diagnostic procedures following UPS failure of 3/6, the affected UPS failed again. This caused a number of single-source power supply servers to crash, most noteably the SIS running on the IBM iSeries (Jenzabar TEAMS 2000), the EMU web server (www.emu.edu) and the Oracle Calendar server.

To prevent this from reoccurring the following servers were moved to the north rack MATRIX UPS: IBM I-series, TS, and Tserve. ZW is still connected to the additional small 280 UPS. All test servers located on the north rack have been powered off – to increase run-time/decrease load on the MATRIX.

APC RMA number: 886725
contact: Ed

The control head has been determined to possibly be the cause due to other issues currently present. A new one is being shipped. We will need to test to see why, when removing the control head, power was lost. We will need to document when this occured – when placed in bypass, when removed, when replaced, etc.

A couple of issues were also discovered in the configuration of the powerchute agent on ZW. This is due to it being a fresh install – use the web client to modify the parameters.

UPS Failure , Several Servers Shutdown

The Matrix UPS providing power to the SOUTH RACK failed at about 8pm, Sun, 3/6. Discovered about 10:45pm. NetSYS tech support switched UPS to BYPASS mode about 11pm.

Servers known to be affected include: Calendar, Mail, DNS, CCTV, FS, FSAPPS. Exact status of servers unknown.

NetSYS techs discussed strategy and decided to take down all servers with single-source powersupplies and switch UPS back to OPERATING mode. This was done and UPS responded appropriately and all seemed to be working normally. Battery at 98%.

Special procedure done to the iSeries (AS400) box (a single-source power supply server). NetSYS worked with Loretta (via phone) to powerdown the unit. Pressed the right button on face plate and power-up proceeded to LOGIN screen on console within 5 minutes.

As a precaution DNS server moved to NORTH Matrix until we are sure all problems with SOUTH Matrix are resolved.

Some additional servers had to be restarted to insure they were running properly. In the course of doing these server restarts it was found that the MAIL server would not start properly. This may be due to changes made last week for the LDAP services. See separate Outage log setup for the MAIL server.